Skip to content

W series outdoor unit (28–56 kW)

W series outdoor unit (28–56 kW)

Heat pump outdoor unit in six capacities for commercial buildings and factories, 28–56 kW; R410A, capacity that grows by combining units.

  • W28
  • W35
  • W40
  • W45
  • W50
  • W56

Highlights

  • Six capacities: 28 / 35 / 40 / 45 / 50 / 56 kW
  • Capacity that grows by combination; units drop out at part load
  • Rated capacity down to −15 °C outdoor air
  • Operation down to −32 °C
  • Water up to 55 °C
  • R410A refrigerant
  • Condenser with epoxy-coated, U-bend copper tubes
  • BLDC fan and DC inverter; compressor insulation and silencer
  • Infrequent defrost with ejector and İYB
  • Building automation, remote monitoring, fault code notification

Applications

  • Hotels and dormitories
  • Business centres and office towers
  • Schools and sports halls
  • Factory office buildings and production areas
  • Central systems for residential complexes
  • Process hot water

The W series covers the heating, cooling and hot water of a commercial building from the same platform. It is built in six capacities: 28 / 35 / 40 / 45 / 50 / 56 kW. For larger demands, several units are run together in combination; when the load falls, some units drop out and efficiency is maintained at part load. All models use R410A refrigerant and DC inverter compressors; water can be heated up to 55 °C.

At low temperatures

The units deliver their rated capacity down to −15 °C outdoor air and keep running until it drops to −32 °C. Thanks to the İYB control working together with the ejector, defrost is needed less often and operation stays stable in cold weather.

Casing

The condenser is made of U-bend copper tubes and coated with epoxy, which reduces the risk of deformation under salt, humidity and other external effects. The speed of the BLDC fan varies with the load, and the compressor compartment has insulation and a silencer.

Monitoring and automation

When a fault occurs, the control board sends the error code both to the indoor units and to the service centre. The system can be connected to building automation and monitored remotely.

For commercial projects

Business centres and office towers, hotels, dormitories, schools, sports halls, the office buildings and production areas of factories, and the central systems of residential complexes are the typical applications of this series. It also serves plants that use hot water in their processes.

Technical data

Scroll the table sideways

ModelW28W35W40W45W50W56
Cooling capacity (kW)4 – 20.84 – 27.54 – 295.2 – 365.8 – 456.9 – 51
Cooling power input, max. (kW)7.28.410.811.412.9513.76
Heating capacity (kW)4.5 – 284.5 – 35.54.7 – 405.8 – 455.8 – 507.2 – 56.6
Heating power input, max. (kW)7.559.111.211.813.1514.6
COP4.394.283.953.953.83.8
Current (A)8.7 – 179.4 – 22.49.8 – 2810.3 – 30.411.5 – 3312.4 – 38
RefrigerantR410AR410AR410AR410AR410AR410A
CompressorDC inverter scrollDC inverter scrollDC inverter scrollDC inverter scrollDC inverter scrollDC inverter scroll
FanBLDCBLDCBLDCBLDCBLDCBLDC
Sound pressure at 1 m (dB(A))43.643.743.746.646.646.6

Request a quote for this product

Tell us the model and the project; we will help you choose the right capacity.

After installation, this product is serviced and maintained by our group company Aktek Elektromekanik. Service by Aktek Elektromekanik

Capacity, quantity, project location and timing help us quote faster.

We use your details only to answer this request. Details are in our privacy notice.

Other products in this group

Heat pumps