Poyraz series heat pump
R290 heat pump for regions where winters stay around −7 °C. 12, 14 and 16 kW models, leaving water up to 55 °C.

Heat pump outdoor unit in six capacities for commercial buildings and factories, 28–56 kW; R410A, capacity that grows by combining units.
The W series covers the heating, cooling and hot water of a commercial building from the same platform. It is built in six capacities: 28 / 35 / 40 / 45 / 50 / 56 kW. For larger demands, several units are run together in combination; when the load falls, some units drop out and efficiency is maintained at part load. All models use R410A refrigerant and DC inverter compressors; water can be heated up to 55 °C.
The units deliver their rated capacity down to −15 °C outdoor air and keep running until it drops to −32 °C. Thanks to the İYB control working together with the ejector, defrost is needed less often and operation stays stable in cold weather.
The condenser is made of U-bend copper tubes and coated with epoxy, which reduces the risk of deformation under salt, humidity and other external effects. The speed of the BLDC fan varies with the load, and the compressor compartment has insulation and a silencer.
When a fault occurs, the control board sends the error code both to the indoor units and to the service centre. The system can be connected to building automation and monitored remotely.
Business centres and office towers, hotels, dormitories, schools, sports halls, the office buildings and production areas of factories, and the central systems of residential complexes are the typical applications of this series. It also serves plants that use hot water in their processes.
Scroll the table sideways
| Model | W28 | W35 | W40 | W45 | W50 | W56 |
|---|---|---|---|---|---|---|
| Cooling capacity (kW) | 4 – 20.8 | 4 – 27.5 | 4 – 29 | 5.2 – 36 | 5.8 – 45 | 6.9 – 51 |
| Cooling power input, max. (kW) | 7.2 | 8.4 | 10.8 | 11.4 | 12.95 | 13.76 |
| Heating capacity (kW) | 4.5 – 28 | 4.5 – 35.5 | 4.7 – 40 | 5.8 – 45 | 5.8 – 50 | 7.2 – 56.6 |
| Heating power input, max. (kW) | 7.55 | 9.1 | 11.2 | 11.8 | 13.15 | 14.6 |
| COP | 4.39 | 4.28 | 3.95 | 3.95 | 3.8 | 3.8 |
| Current (A) | 8.7 – 17 | 9.4 – 22.4 | 9.8 – 28 | 10.3 – 30.4 | 11.5 – 33 | 12.4 – 38 |
| Refrigerant | R410A | R410A | R410A | R410A | R410A | R410A |
| Compressor | DC inverter scroll | DC inverter scroll | DC inverter scroll | DC inverter scroll | DC inverter scroll | DC inverter scroll |
| Fan | BLDC | BLDC | BLDC | BLDC | BLDC | BLDC |
| Sound pressure at 1 m (dB(A)) | 43.6 | 43.7 | 43.7 | 46.6 | 46.6 | 46.6 |
Tell us the model and the project; we will help you choose the right capacity.
After installation, this product is serviced and maintained by our group company Aktek Elektromekanik. Service by Aktek Elektromekanik

R290 heat pump for regions where winters stay around −7 °C. 12, 14 and 16 kW models, leaving water up to 55 °C.

R290 heat pump with vapour injection for long, harsh winters: 65 °C leaving water at −25 °C outdoor air, 12–16 kW.

R32 heat pump for coastal climates, with mild winters and long, hot summers. 12–16 kW heating at +2 °C outdoor air, strong cooling.

R290 + R134a cascade heat pump for Eastern Anatolia and high altitude. 75 °C water at −30 °C outdoor air, 12–16 kW, buffer tank inside.