Poyraz series heat pump
R290 heat pump for regions where winters stay around −7 °C. 12, 14 and 16 kW models, leaving water up to 55 °C.

20 and 24 kW heat pump outdoor unit: rated capacity down to −15 °C, three-phase, R410A, DC inverter. For villas, small residential complexes and commercial premises.
The V series is for projects that go beyond residential scale but do not need a central system: a large or semi-detached villa, a small residential complex, a restaurant, shop, showroom, small hotel, guesthouse or office floor. It is built in two capacities, 20 and 24 kW; both run on three-phase power, and the leaving water temperature can reach 55 °C. It has a split design: data between the indoor and outdoor units is exchanged over a serial communication line.
The unit maintains its rated capacity down to −15 °C; its operating limit is −32 °C. The ejector and İYB control delay defrosting: the unit goes into defrost less often, and the loss of efficiency at low outdoor temperatures stays limited.
The condenser is made of O-bend copper tubes and coated with epoxy. It resists the corrosion caused by salt, humidity and dust by the sea and in industrial zones, which extends its life. The speed of the BLDC fan varies with demand. The DC inverter compressor runs in an insulated compartment with a silencer; the sound level is low enough for the unit to be placed below a window.
When the control board detects a fault, it sends the fault code to the indoor unit; if required, the same information also reaches the service centre by e-mail.
| Model | V20 | V24 |
|---|---|---|
| Cooling capacity (kW) | 4 – 16 | 5.2 – 20 |
| Cooling power input, max. (kW) | 4.9 | 5.7 |
| Heating capacity (kW) | 4.5 – 20.96 | 5.4 – 24.1 |
| Heating power input, max. (kW) | 5.1 | 6.5 |
| COP | 4.38 | 4.28 |
| Current (A) | 6 – 14 | 7.5 – 15.2 |
| Power supply | 380–400 V / 3 phase | 380–400 V / 3 phase |
| Refrigerant | R410A | R410A |
| Compressor | DC inverter scroll | DC inverter scroll |
| Fan | BLDC | BLDC |
| Sound pressure at 1 m (dB(A)) | 43 – 54 | 43 – 54 |
| Unit dimensions W × D × H (mm) | 610 × 610 × 735 | 710 × 710 × 810 |
| Weight (kg) | 156 | 169 |
Tell us the model and the project; we will help you choose the right capacity.
After installation, this product is serviced and maintained by our group company Aktek Elektromekanik. Service by Aktek Elektromekanik

R290 heat pump for regions where winters stay around −7 °C. 12, 14 and 16 kW models, leaving water up to 55 °C.

R290 heat pump with vapour injection for long, harsh winters: 65 °C leaving water at −25 °C outdoor air, 12–16 kW.

R32 heat pump for coastal climates, with mild winters and long, hot summers. 12–16 kW heating at +2 °C outdoor air, strong cooling.

R290 + R134a cascade heat pump for Eastern Anatolia and high altitude. 75 °C water at −30 °C outdoor air, 12–16 kW, buffer tank inside.